6.6.3 System-Stopped/Cold Removal Workflow of the CMUU
6.6.3 System-Stopped/Cold Removal Workflow of the CMUU
Before removing the CMUU, see "Precautions for CMUU removal" in "7.3 Precautions for FRU Reduction."
Table 6-24 shows the workflow for system-stopped/cold removal of the CMUU.
Work Order | Task | Reference |
---|---|---|
1 | Checking the operating condition of the system | "9.2.1 Checking the Operation Status of Physical Partitions and Logical Domains" |
2 | Releasing the assignment of the CPU and memory resources of the CMUU to be removed | "Chapter 3 Operations for Domain Configuration" in the Fujitsu SPARC M12 and Fujitsu M10/SPARC M10 Domain Configuration Guide |
3 | Confirming that you can remove the CMUU to be removed (*1) | "9.2.1 Checking the Operation Status of Physical Partitions and Logical Domains" |
4 | Saving logical domain configuration information | "9.1.1 Saving Logical Domain Configuration Information" |
5 | Powering off all physical partitions | "9.5.2 Stopping All Physical Partitions" |
6 | Switching the mode switch on the OPNL to Service | "2.3.2 OPNL Control Function" |
7 | Removing the power cords of all the SPARC M12-2/M12-2S units | "9.8.2 Removing the Power Cords" |
8 | Enabling the removal of the CMUU | "17.4.1 Enabling the Removal of the CMU" |
9 | Removing the CMUU from the SPARC M12-2/M12-2S | "17.4.2 Removing the CMU" |
10 | Installing the filler unit in the SPARC M12-2/M12-2S | "17.5.2 Installing the CMU" |
11 | Assembling the SPARC M12-2/M12-2S from which the CMUU was removed | "17.5.3 Restoring the Server" |
12 | Installing the power cords of all the SPARC M12-2/M12-2S units | "10.1.1 Installing a Power Cord" |
13 | Diagnosing all the SPARC M12-2/M12-2S units | "10.5.1 Diagnosing the SPARC M12 Hardware" |
14 | Confirming that there is no problem with the system from which the CMUU was removed | "10.5.3 Checking the FRU Status After Maintenance" |
15 | Reconfiguring the I/O bus as required (*2) | "3.2.18 Configuring an I/O Device" in the Fujitsu SPARC M12 and Fujitsu M10/SPARC M10 Domain Configuration Guide |
16 | Switching the mode switch on the OPNL to Locked | "2.3.2 OPNL Control Function" |
17 | Powering on all physical partitions | "10.9.1 Starting the System With an XSCF Command" |
18 | Checking the operating condition of the physical partition and logical domains (*1) | "9.2.1 Checking the Operation Status of Physical Partitions and Logical Domains" |
19 | Saving logical domain configuration information | "9.1.1 Saving Logical Domain Configuration Information" |
*1 Reconfigure logical domains as required. For details, see "Chapter 5 Logical Domain Configuration Example" in the Fujitsu SPARC M12 and Fujitsu M10/SPARC M10 Domain Configuration Guide. *2 When reconfiguring the I/O bus, you may need to reconfigure the logical domains. |