  9. 6.2.2 Incorporation of the power supply unit and fan unit of the SPARC M10-4/M10-4S

6.2.2 Incorporation of the power supply unit and fan unit of the SPARC M10-4/M10-4S


6.2.2 Incorporation of the power supply unit and fan unit of the SPARC M10-4/M10-4S
This section describes the procedure for incorporating a FRU into the system after maintenance.
After replacing the FRU in step 7 in "5.8.2 Releasing of the power supply unit and fan unit of the SPARC M10-4/M10-4S," continue here.
  1. After completing maintenance of the target FRU, return to the replacefru command operation of the XSCF firmware, and enter "f".
    After maintenance on the power supply unit (PSU), connect the power cord. Then, after 10 seconds elapse, enter "f".
Please execute the following steps:
1) Remove BB#0/PSU#0.
2) Execute either the following:
2-1) After installing the exchanged device, please select 'finish'.
2-2) If you want to suspend the maintenance without exchanging device,
please select 'cancel'.
[f:finish|c:cancel] :f
  1. Entering "f" displays the following screen. Wait until the processing has completed.
Waiting for BB#0/PSU#0 to enter install state.
[This operation may take up to 10 second(s)]
(progress scale reported in seconds)
0.done
Diagnostic tests for BB#0/PSU#0 have started.
[This operation may take up to 2 minute(s)]
(progress scale reported in seconds)
0..done
  1. Confirm that the status is normal ("Normal") after the replacement, and then enter "f".
------------------------------------------------------------------------------

Maintenance/Replacement Menu
Status of the replaced FRU.

FRU Status
------------------- --------------

/BB#0/PSU#0 Normal
------------------------------------------------------------------------------

The replacement of BB#0/PSU#0 has completed normally.[f:finish] :f
  1. When the maintenance menu appears, enter "c" to exit the operation.
------------------------------------------------------------------------------

Maintenance/Replacement Menu
Please select the chassis including replaced FRU.
No. FRU Status
--- ------------------- --------------

1 /BB#0 Normal

2 /BB#1 Unmount

3 /BB#2 Unmount

4 /BB#3 Unmount

------------------------------------------------------------------------------

Select [1-4|c:cancel] :c