Skip to main content

2.9.2 Power cord specifications


2.9.2 Power cord specifications
Table 2-14 and Table 2-15 list the power cords and connector shape for each chassis.
Table 2-16 lists the power cords and connector shape of the PDU for the expansion rack used to connect five or more SPARC M10-4S units.
Table 2-14  Power cords and connector shape (SPARC M10-4S)
Destination Power cord type Connector shape
Japan IEC60320-C20 250V 16A
NEMA L6-20P 250V 20A
IEC 60320-C19
North America IEC60320-C20 250V 16A
NEMA L6-20P 250V 20A
IEC60309 250V 16A
 
South America IEC60309 250V 16A  
China IEC60309 250V 16A  
Hong Kong IEC60309 250V 16A  
Taiwan NEMA L6-20P 250V 20A  
Korea NEMA L6-20P 250V 20A  
India IS1293 250V 16A  
Other countries IEC60309 250V 16A  
Table 2-15  Power cords and connector shape (PCI expansion unit)
Destination Power cord type Connector shape
Japan NEMA 5-15P 125V 15A
NEMA L6-15P 250V 15A
IEC 60320-C13
North America NEMA 5-15P 125V 15A
NEMA L6-15P 250V 15A
IEC60320-C14 250V 10A
 
South America IRAM2073 250V 10A
NBR14136 250V 10A
 
China GB2099.1 250V 10A  
Hong Kong BSI363A 250V 10A  
Taiwan CNS10917 250V 10A  
Korea KSC8305 250V 10A  
India IS1293 250V 16A  
Other countries IEC60309 250V 10A
IEC60320-C14 250V 10A
 
Table 2-16  Power cords and connector shape (PDU of an expansion rack)
Destination Power cord type Connector shape
Common For 200 V power supply (*1)
- For single-phase power supply connection

 IEC60309 60A 2P+E
- For three-phase delta connection

 IEC60309 60A 3P+E
- For three-phase star connection

 IEC60309 30A 3P+N+E
 IEC60309 32A 3P+N+E
IEC60320-C20
*1 The following two types of power cords are necessary for each chassis mounted in an expansion rack: 0.5 m (1.6 ft.) and 1.5 m (4.9 ft.) power cords. The customer needs to order these power cords for each chassis.
Note - For chassis with plugs that have a lock function, confirm that the chassis have a 15 A (20 A for the SPARC M10-4S) overcurrent protection device. If they do not have that device, provide 15 A (20 A for SPARC M10-4S) overcurrent protection using a circuit breaker or fuse. The plugs with a lock function are the NEMA L6-20, L6-15, and other plugs that are not parallel two-pole connectors with grounding electrodes.