2.9.1 Electrical specifications
2.9.1 Electrical specifications
Table 2-9 to Table 2-13 list the electrical specifications of each chassis.
Note - The values listed in Table 2-9 to Table 2-13 are based on values for the maximum configuration of each chassis. The actual values vary depending on the system configuration. |
Item | Specification | |
---|---|---|
CPU type: SPARC64 X | CPU type: SPARC64 X+ | |
Input voltage | 200 to 240 VAC |
|
Number of power cords | 2 (1 for each PSU) |
|
Power cord length | Maximum length of 3.0 m (9.8 ft.) | |
Redundancy | 1+1 redundant configuration | |
Frequency | 50 Hz/60 Hz, single phase |
|
Maximum input current (*1) | 14.8 A | 16.0 A |
Maximum power consumption | 2,905 W | 3,425 W |
Apparent power | 2,964 VA | 3,495 VA |
Rush current (*2) | 45 A peak or less |
|
Leakage current (*2) | 1.75 mA or less | |
*1 The current that flows through each power cord in a redundant configuration is half the value listed in Table 2-9. *2 The value is per power cord. |
Item | Specification | |
---|---|---|
Expansion rack 1 only | Including expansion rack 2 | |
Input voltage | 200 to 240 VAC |
200 to 240 VAC |
Number of power cords | 8 | 8 |
Power cord length | 4.0 m (13.1 ft.) | 4.0 m (13.1 ft.) |
Redundancy (*2) | 1+1 redundant configuration | 1+1 redundant configuration |
Frequency | 50 Hz/60 Hz |
50 Hz/60 Hz |
Maximum input current (*3)(*4)(*5) | 6.9 A | 9.0 A |
Maximum power consumption (*4) | 1,354 W | 1,754 W |
Apparent power (*4) | 1,382 VA | 1,790 VA |
Rush current (*4) | 160 A peak or less |
160 A peak or less |
Leakage current (*4) | 7.0 mA or less | 7.0 mA or less |
*1 The specifications apply to a single rack. *2 For the SPARC M10-4S mounted in an expansion rack. If the mounted device is not the SPARC M10-4S, the configuration may be different depending on the power connection configuration of the device. *3 When the SPARC M10-4S is mounted in the expansion rack, the tolerance per power cord is a value of 40 A. For details on the device connected to each power cord, see Figure 2-22. *4 The value is for an expansion rack without the SPARC M10-4S and other devices mounted. (Only crossbar boxes are mounted.) Only four power cords consume power. If the SPARC M10-4S or other devices are mounted, the current values and the number of power cords that consume power are different. *5 The current that flows through each power cord in a redundant configuration is half the value listed in Table 2-10. |
Item | Specification | |
---|---|---|
Expansion rack 1 only | Including expansion rack 2 | |
Input voltage | 200 to 240 VAC |
200 to 240 VAC |
Number of power cords | 6 | 6 |
Power cord length | 4.0 m (13.1 ft.) | 4.0 m (13.1 ft.) |
Redundancy (*2) | 1+1 redundant configuration | 1+1 redundant configuration |
Frequency | 50 Hz/60 Hz |
50 Hz/60 Hz |
Maximum input current (*3)(*4)(*5) | 4.0 A | 5.2 A |
Maximum power consumption (*4) | 1,354 W | 1,754 W |
Apparent power (*4) | 1,382 VA | 1,790 VA |
Rush current (*4) | 160 A peak or less |
160 A peak or less |
Leakage current (*4) | 7.0 mA or less | 7.0 mA or less |
*1 The specifications apply to a single rack. *2 For the SPARC M10-4S mounted in an expansion rack. If the mounted device is not the SPARC M10-4S, the configuration may be different depending on the power connection configuration of the device. *3 When the SPARC M10-4S is mounted in the expansion rack, the tolerance per power cord is a value of 35 A. For details on the device connected to each power cord, see Figure 2-23. *4 The value is for an expansion rack without the SPARC M10-4S and other devices mounted. (Only crossbar boxes are mounted.) Only four power cords consume power. If the SPARC M10-4S or other devices are mounted, the current values and the number of power cords that consume power are different. *5 The current that flows through each power cord in a redundant configuration is half the value listed in Table 2-11. |
Item | Specification | |
---|---|---|
Expansion rack 1 only | Including expansion rack 2 | |
Input voltage | 380 to 415 VAC |
380 to 415 VAC |
Number of power cords | 6 | 6 |
Power cord length | 4.0 m (13.1 ft.) | 4.0 m (13.1 ft.) |
Redundancy (*2) | 1+1 redundant configuration | 1+1 redundant configuration |
Frequency | 50 Hz/60 Hz |
50 Hz/60 Hz |
Maximum input current (*3)(*4)(*5) | 2.1 A | 2.7 A |
Maximum power consumption (*4) | 1,354 W | 1,754 W |
Apparent power (*4) | 1,382 VA | 1,790 VA |
Rush current (*4) | 160 A peak or less |
160 A peak or less |
Leakage current (*4) | 7.0 mA or less | 7.0 mA or less |
*1 The specifications apply to a single rack. *2 For the SPARC M10-4S mounted in an expansion rack. If the mounted device is not the SPARC M10-4S, the configuration may be different depending on the power connection configuration of the device. *3 When the SPARC M10-4S is mounted in the expansion rack, the tolerance per power cord is a value of 24 A. For details on the device connected to each power cord, see Figure 2-23. *4 The value is for an expansion rack without the SPARC M10-4S and other devices mounted. (Only crossbar boxes are mounted.) Only four power cords consume power. If the SPARC M10-4S or other devices are mounted, the current values and the number of power cords that consume power are different. *5 The current that flows through each power cord in a redundant configuration is half the value listed in Table 2-12. |
Item | Specification | |
---|---|---|
Input voltage of 100 to 120 VAC | Input voltage of 200 to 240 VAC | |
Number of power cords | 2 (1 for each PSU) |
2 (1 for each PSU) |
Power cord length | Maximum length of 3.0 m (9.8 ft.) | Maximum length of 3.0 m (9.8 ft.) |
Redundancy | 1+1 redundant configuration | 1+1 redundant configuration |
Frequency | 50 Hz/60 Hz, single phase |
50 Hz/60 Hz, single phase |
Maximum input current (*1) | 2.9 A | 1.4 A |
Maximum power consumption | 279 W | 270 W |
Apparent power | 284 VA |
276 VA |
Rush current (*2) | 40 A peak or less |
40 A peak or less |
Leakage current (*2) | 1.75 mA or less | 1.75 mA or less |
*1 The current that flows through each power cord in a redundant configuration is half the value listed in Table 2-13. *2 The value is per power cord. |