2.9.2 Power Cord Specifications


2.9.2 Power Cord Specifications
Table 2-14 and Table 2-15 list the power cords and connector shapes for the SPARC M12-2S and PCI expansion unit. Table 2-16 lists the power cords and connector shapes for the PDU of the expansion rack used to connect five or more SPARC M12-2S units.
Table 2-14  Power Cords and Connector Shapes (SPARC M12-2S)
Destination Power Cord Type Connector Shape
Japan NEMA L6-15P 250V 15A IEC 60320-C13
North America NEMA L6-15P 250V 15A IEC 60320-C13
Europe CEE7/7  
U.K. BS1363A  
Italy CEI 23-16/Ⅶ  
China GB 2099 250V  
Taiwan CNS10917  
Korea KSC 8305 250V  
Denmark DEMKO 107  
Israel SI 32  
India IS 1293  
South Africa SABS 164  
Argentina IRAM2073 250V  
Australia AS/NZS 3112  
Brazil NBR14136 250V  
Switzerland SEV 1011  
Other countries IEC60309 IP44 250V 10A
IEC60320-C14 250V 10A
 
Common (*1)
(Jumper cord)
IEC60320-C14 250V 10A  
*1 Four power cords are required per SPARC M12-2S mounted in an expansion rack: two are 1.0 m (3.3 ft.) long, and the other two are 2.0 m (6.6 ft.) long. Enough for the number of SPARC M12-2S units needs to be ordered separately.
Table 2-15  Power Cords and Connector Shapes (PCI Expansion Unit)
Destination Power Cord Type Connector Shape
Japan NEMA 5-15P 125V 15A
NEMA L6-15P 250V 15A
IEC 60320-C13
North America NEMA 5-15P 125V 15A
NEMA L6-15P 250V 15A
IEC60320-C14 250V 10A
 
Europe CEE7/7  
U.K. BS1363A  
Italy CEI 23-16/Ⅶ  
China GB 2099 250V  
Taiwan CNS10917  
Korea KSC 8305 250V  
Denmark DEMKO 107  
Israel SI 32  
India IS 1293  
South Africa SABS 164  
Argentina IRAM2073 250V  
Australia AS/NZS 3112  
Brazil NBR14136 250V  
Switzerland SEV 1011  
Other countries IEC60309 IP44 250V 10A
IEC60320-C14 250V 10A
 
Table 2-16  Power Cord Plug Types (Expansion Rack PDU)
Destination Power Cord Type
Common For 200 V power
- Single-phase power supply connection

 IEC60309 IP67 60A 2P+E
- Three-phase delta connection

 IEC60309 IP67 60A 3P+E
- Three-phase star connection

 IEC60309 IP44 32A 3P+N+E
Note - For chassis with plugs that have a lock function, confirm that the chassis have a 15 A overcurrent protection device. If they do not have that device, provide 15 A overcurrent protection using a circuit breaker or fuse. The plugs with a lock function are NEMA L6-15 and other plugs that are not parallel two-pole connectors with grounding electrodes.