19.4 Installing the Crossbar Backplane Unit
19.4 Installing the Crossbar Backplane Unit
This section describes the procedure for installing the crossbar backplane unit.
- Insert the crossbar backplane unit into the chassis, and tighten the five screws.
- Fix the cables of the crossbar backplane unit with the clamps.
- Install the guide plate by sliding it toward the rear, and tighten the two screws.
Check the guide plate latch to ensure that the plate is securely installed. - Support the fan shelf from below with one hand, and carefully insert it into the chassis.
Arranging the cables in the center makes it easier to install the fan shelf. - Tighten the three screws securing the fan shelf.
- Connect the two cables to the fan shelf.
- Install the lower cover, and secure it with one screw.
- Install the upper cover.
- Slide the right and left stoppers of the upper cover outward, and secure the cover with two screws.
- Install all the fan units.
For details, see "15.4 Installing a Fan Unit." - Install the front cover.
For details, see "6.1.2 Installing the Front Cover." - Reinstall the following components in their original positions in the order shown.- Power supply unit
For details, see "13.4 Installing a Power Supply Unit."- Crossbar unit or filler unit of the crossbar unit
For details, see "12.4 Installing a Crossbar Unit."- XSCF interface unit
For details, see "14.5 Installing the XSCF Interface Unit."- XSCF unit
For details, see "8.6 Installing the XSCF Unit."
The FRU installation work is completed. See "Chapter 7 Maintenance Flow" to continue maintenance work.