2.9.1 Electrical Specifications
2.9.1 Electrical Specifications
Item | SPARC M12-2 (16 memory slots) | SPARC M12-2 (24 memory slots) |
---|---|---|
Input voltage | 200 to 240 VAC |
200 to 240 VAC |
Number of power cords | 4 (1 for each PSU) |
4 (1 for each PSU) |
Power cord length | Maximum length of 3.0 m (9.8 ft.) | Maximum length of 3.0 m (9.8 ft.) |
Redundancy | 2+2 redundant configuration | 2+2 redundant configuration |
Frequency | 50 Hz/60 Hz, single phase |
50 Hz/60 Hz, single phase |
Maximum input current (*1) | 14.8 A | 15.2 A |
Maximum power consumption | 2,906 W | 2,974 W |
Apparent power | 2,965 VA | 3,035 VA |
Rush current (*2) | 65 A peak or less |
65 A peak or less |
Leakage current (*2) | 3.5 mA or less | 3.5 mA or less |
*1 The current that flows through each power cord is a fraction of the value listed in Table 2-8. In a redundant configuration, it is one-fourth the value. In a non-redundant configuration, it is up to one-half the value. *2 The value is per power cord. |
Item | Specification | |
---|---|---|
Input voltage of 100 to 120 VAC | Input voltage of 200 to 240 VAC | |
Number of power cords | 2 (1 for each PSU) |
2 (1 for each PSU) |
Power cord length | Maximum length of 3.0 m (9.8 ft.) | Maximum length of 3.0 m (9.8 ft.) |
Redundancy | 1+1 redundant configuration | 1+1 redundant configuration |
Frequency | 50 Hz/60 Hz, single phase |
50 Hz/60 Hz, single phase |
Maximum input current (*1) | 2.9 A | 1.4 A |
Maximum power consumption | 279 W | 270 W |
Apparent power | 284 VA |
276 VA |
Rush current (*2) | 40 A peak or less |
40 A peak or less |
Leakage current (*2) | 1.75 mA | 1.75 mA |
*1 The current that flows through each power cord in a redundant configuration is half the value listed in Table 2-9. *2 The value is per power cord. |