Skip to main content
  1. Home >
  2. Products >
  3. Computing Products >
  4. Servers >
  5. Fujitsu SPARC servers >
  6. Downloads >
  7. User Manuals >
  8. Fujitsu SPARC M12-1 Installation Guide >
  9. 2.4.2 Installation Area for a General Rack

2.4.2 Installation Area for a General Rack


2.4.2 Installation Area for a General Rack
Service areas
Service area requirements vary depending on the rack used.
When mounting each chassis in the designated rack, see the examples of service areas in Figure 2-3 and Figure 2-5. The rack width depends on the rack used.
When using a rack other than the designated rack, see the manual for the rack used.
Figure 2-3  Example of Service Areas for the SPARC M12-1 (Top View)
Figure 2-3  Example of Service Areas for the SPARC M12-1 (Top View)
*1 This area is required on either the left or right side.
*2 To mount a chassis on the rack, an area with a depth of 1,200 mm (47.2 in.) is required in front of the rack.
If there is a possibility that a chassis will be added later, secure an area with a depth of 1,200 mm (47.2 in.) in front of the rack.
Figure 2-4  Example of Service Areas for the SPARC M12-1 When Using a Stepladder (Top View)
Figure 2-4  Example of Service Areas for the SPARC M12-1 When Using a Stepladder (Top View)
*1 This area is required for using a stepladder, and it differs depending on the stepladder used. Referring to the above figure, ensure that the service area is appropriate to the stepladder used. This area is required on either the left or right side.
*2 To mount a chassis in the rack, an area with a depth of 1,200 mm (47.2 in.) is required in front of the rack.
If there is a possibility that a chassis will be added later, secure an area with a depth of 1,200 mm (47.2 in.) in front of the rack.
Figure 2-5  Example of Service Areas for the PCI Expansion Unit (Top View)
Figure 2-5  Example of Service Areas for the PCI Expansion Unit (Top View)
*1 To mount a chassis in the rack, an area with a depth of 1,200 mm (47.2 in.) is required in front of the rack, and areas with a width of 600 mm (23.6 in.) are required on both the left and right sides of the front service area. If there is a possibility that a chassis will be added later, secure an area with a depth of 1,200 mm (47.2 in.) in front of the rack and areas with a width of 600 mm (23.6 in.) on both the left and right sides of the front service area.