2.5.3 Contaminant conditions
2.5.3 Contaminant conditions
Table 2-5 provides the acceptable reference values for contaminants with regard to the SPARC M10 systems.
Contaminant | Acceptable reference value |
---|---|
Hydrogen sulfide (H2S) | 7.1 ppb or less |
Sulfurous acid gas (sulfur oxide) (SO2) | 37 ppb or less |
Hydrogen chloride (HCI) | 6.6 ppb or less |
Chlorine (CI2) | 3.4 ppb or less |
Hydrogen fluoride (HF) | 3.6 ppb or less |
Nitrogen dioxide (nitrogen oxide) (NO2) | 52 ppb or less |
Ammonia (NH3) | 420 ppb or less |
Ozone (O3) | 5 ppb or less |
Oil vapor | 0.2 mg/m3 or less |
Dust | 0.15 mg/m3 or less |
Seawater (salt damage) | Do not install out at sea or within 500 m (1,640.4 ft.) of the seashore. (However, this does not apply if air conditioning facilities do not use outside air.) |